07 — Cascaded Control Loops

Current inside speed inside position — three PIDs, one motor

Prerequisite: 06-fixed-point-pid.md (fixed-point PID), 05-mcu-motor-control.md (hardware) Unlocks: 08-trajectory-tracking.md (what feeds the position/speed commands)


Why Should I Care? (Practical Context)

A single PID controlling motor speed from voltage is okay for a toy. For an warehouse robot carrying 200 kg at 1 m/s, you need cascaded loops: an inner current (torque) loop, a middle speed loop, and an outer position loop. Each loop handles a different timescale and gives you independent control over torque, speed, and position.

Why cascade matters in practice: - Without current limiting → motor stall at startup = 15A peak → trips the battery BMS → e-stop - Without speed limiting → acceleration spike → load slides off the shelf - Without position loop → can’t hold position at a station (drift on slopes)

AMR cascade architecture:

Nav2 → position_cmd (50 Hz)
          ↓
     Position PID (1 kHz)
          ↓ speed_cmd
     Speed PID (10 kHz)
          ↓ current_cmd
     Current PID (20 kHz)
          ↓ duty
     PWM → H-Bridge → Motor

PART 1 — WHY CASCADE?

1.1 The Problem with a Single Loop

A single PID from position to PWM duty:

$$u = K_p(r - \theta) + K_i \int(r - \theta)dt + K_d \frac{d(r - \theta)}{dt}$$

Problems: 1. Can’t limit current: The PID output is a duty cycle. If the position error is large, the duty goes to 100%, drawing unlimited current. 2. Slow response to disturbances: If the load suddenly increases, the motor slows. The position PID notices… eventually… after the position has drifted. By then, the error is large and the response is aggressive. 3. Can’t independently tune torque, speed, and position: You have 3 gains but 3 different dynamic behaviors to control.

1.2 The Cascade Solution

Each loop controls one physical quantity and limits it:

Loop Controls Limits Rate Bandwidth
Current (inner) Motor current → torque Max current (e.g., 5A) 20 kHz ~2 kHz
Speed (middle) Motor speed Max speed (e.g., 100 RPM at wheel) 10 kHz ~50 Hz
Position (outer) Wheel/robot position Max speed command 1 kHz ~5 Hz

The 10:1 bandwidth rule: Each outer loop should have bandwidth ≤ 1/10 of the inner loop. This ensures the inner loop “looks like a gain of 1” to the outer loop (it’s so fast that it perfectly tracks its setpoint).

$$f_{BW,outer} \leq \frac{1}{10} f_{BW,inner}$$


PART 2 — THE CURRENT (TORQUE) LOOP

2.1 Purpose

The current loop: 1. Makes the motor behave like a torque source (command current → get torque) 2. Protects against overcurrent (hard-limits current even if speed PID demands more) 3. Rejects electrical disturbances (back-EMF changes) fast

2.2 Plant Model

The motor’s electrical equation:

$$V = Ri + L\frac{di}{dt} + K_e \omega$$

From the current loop’s perspective, $K_e \omega$ is a disturbance (back-EMF). The “plant” is:

$$G_i(s) = \frac{I(s)}{V(s)} = \frac{1/R}{\frac{L}{R}s + 1} = \frac{1/R}{\tau_e s + 1}$$

where $\tau_e = L/R$ is the electrical time constant (~0.5 ms for robot motor).

2.3 PI Controller (No D)

The current loop uses PI only (no derivative) because: - The electrical dynamics are fast and noisy - Derivative amplifies current sensor noise - PI is sufficient for first-order plant + disturbance rejection

$$C_i(s) = K_{p,i} + \frac{K_{i,i}}{s}$$

Tuning by pole placement: Place the closed-loop pole at $f_{cl} = 2$ kHz ($\omega_{cl} = 4000\pi$ rad/s):

$$K_{p,i} = L \cdot \omega_{cl} = 0.001 \times 4000\pi = 12.57$$

$$K_{i,i} = R \cdot \omega_{cl} = 1.0 \times 4000\pi = 12566$$

This cancels the plant pole (zero of PI at $R/L$ cancels pole at $R/L$), leaving a first-order closed-loop with bandwidth $\omega_{cl}$.

2.4 Implementation

// Current PID — runs at 20 kHz
// PI only, velocity form
typedef struct {
    q16_t Kp;
    q16_t Ki_Ts;        // Ki × Ts pre-multiplied
    q16_t prev_error;
    q16_t output;
    q16_t output_min;   // = -MAX_DUTY (Q16.16)
    q16_t output_max;   // = +MAX_DUTY (Q16.16)
} CurrentPI;

q16_t current_pi_compute(CurrentPI *pi, q16_t current_cmd, q16_t current_meas) {
    q16_t error = current_cmd - current_meas;

    // Velocity form: Δu = Kp*(e - e_prev) + Ki*Ts*e
    q16_t delta_u = q16_mul(pi->Kp, error - pi->prev_error)
                  + q16_mul(pi->Ki_Ts, error);

    pi->output = q16_add_sat(pi->output, delta_u);

    // Clamp to valid duty cycle
    if (pi->output > pi->output_max) pi->output = pi->output_max;
    if (pi->output < pi->output_min) pi->output = pi->output_min;

    pi->prev_error = error;
    return pi->output;  // This is the PWM duty cycle
}

PART 3 — THE SPEED LOOP

3.1 Purpose

The speed loop: 1. Makes the motor behave like a speed source (command speed → get speed) 2. Limits acceleration (rate-limits the current command) 3. Compensates for load torque disturbances

3.2 Plant Model

From the speed loop’s perspective, the current loop is fast enough to be “transparent” (gain ≈ 1). The “plant” is the motor’s mechanical dynamics:

$$G_\omega(s) = \frac{\Omega(s)}{T(s)} = \frac{1/B}{Js/B + 1} = \frac{1/B}{\tau_m s + 1}$$

where $\tau_m = J/B$ is the mechanical time constant (~50 ms for the robot with gearbox).

But since the current loop output → torque: $T = K_t \times i$, the combined plant is:

$$G_\omega(s) = \frac{K_t}{Js + B}$$

3.3 PI Controller

Again PI only, because: - Speed from encoder is noisy (quantization) - D term amplifies encoder noise → duty cycle jitter → audible motor whine

Tuning: Bandwidth ≤ 1/10 of current loop = 200 Hz max. Target: ~50 Hz.

$$K_{p,\omega} = \frac{J \cdot \omega_{BW}}{K_t} = \frac{0.001 \times 100\pi}{0.05} = 6.28$$

$$K_{i,\omega} = \frac{B \cdot \omega_{BW}}{K_t} = \frac{0.002 \times 100\pi}{0.05} = 12.57$$

3.4 Output of Speed PID = Current Setpoint

// Speed PID — conceptually at 10 kHz (or 1 kHz with feedforward)
q16_t speed_pid_compute(SpeedPID *pid, q16_t speed_cmd, q16_t speed_meas) {
    q16_t error = speed_cmd - speed_meas;

    // Standard velocity-form PI
    q16_t delta_u = q16_mul(pid->Kp, error - pid->prev_error)
                  + q16_mul(pid->Ki_Ts, error);

    pid->output = q16_add_sat(pid->output, delta_u);

    // Clamp to MAX CURRENT (this is the safety limit!)
    if (pid->output > pid->current_limit_pos) pid->output = pid->current_limit_pos;
    if (pid->output < pid->current_limit_neg) pid->output = pid->current_limit_neg;

    pid->prev_error = error;
    return pid->output;  // This is the current setpoint for the inner loop
}

Critical point: The speed PID output is clamped to the maximum allowed current, not the maximum PWM duty. This is how cascade provides current limiting — the speed loop can never ask for more current than the motor/driver can safely handle.


PART 4 — THE POSITION LOOP

4.1 Purpose

The position loop: 1. Tracks a position trajectory (for docking, station alignment) 2. Holds position against external disturbances (slopes, impacts) 3. Limits speed (the position PID output = speed command)

4.2 Plant Model

From the position loop’s perspective, the speed loop is a perfect speed source (gain ≈ 1). The “plant” is just integration:

$$\frac{\Theta(s)}{\Omega(s)} = \frac{1}{s}$$

An integrator — infinite DC gain already, so:

4.3 P Controller (Often Sufficient!)

For a pure integrator plant, a simple proportional controller gives first-order closed-loop response:

$$C_{pos}(s) = K_{p,pos}$$

$$G_{cl}(s) = \frac{K_{p,pos}/s}{1 + K_{p,pos}/s} = \frac{K_{p,pos}}{s + K_{p,pos}}$$

Bandwidth = $K_{p,pos}$ rad/s. For 5 Hz bandwidth: $K_{p,pos} = 10\pi \approx 31$.

Why no I term? The plant itself is an integrator (speed → position). Adding I to the controller means double integration → 180° phase lag → stability problems. Use I only if there’s a steady-state position error (e.g., friction preventing final positioning).

Why no D term? D on position = a speed feedforward, which can be useful but makes tuning harder. Usually handled separately as explicit feedforward (see Lesson 08).

4.4 Implementation

// Position PID — runs at 1 kHz
// P-only with optional feedforward
q16_t position_pid_compute(PositionPID *pid, q16_t pos_cmd, q16_t pos_meas,
                           q16_t feedforward_speed) {
    q16_t error = pos_cmd - pos_meas;

    // P-only
    q16_t speed_cmd = q16_mul(pid->Kp, error) + feedforward_speed;

    // Clamp to MAX SPEED
    if (speed_cmd > pid->speed_limit_pos) speed_cmd = pid->speed_limit_pos;
    if (speed_cmd < pid->speed_limit_neg) speed_cmd = pid->speed_limit_neg;

    return speed_cmd;  // This is the speed setpoint for the middle loop
}

PART 5 — BANDWIDTH SEPARATION AND TUNING ORDER

5.1 Bandwidth Summary

Position loop: 5 Hz bandwidth → responds in ~50 ms
    │
    │ 10× separation
    ▼
Speed loop: 50 Hz bandwidth → responds in ~5 ms
    │
    │ 10× separation (at least)
    ▼
Current loop: 2 kHz bandwidth → responds in ~0.15 ms

5.2 Tuning Order (CRITICAL)

Always tune from the inside out:

  1. Current loop first — disconnect speed loop, command current directly, verify step response
  2. Speed loop second — keep current loop tuned, disconnect position loop, command speed directly
  3. Position loop last — keep everything tuned, command position

Why inside-out? Each outer loop assumes the inner loop is already working. If you tune the speed loop with a badly-tuned current loop, you’re compensating for the current loop’s errors — and everything breaks when you fix the current loop later.

5.3 Practical Tuning Procedure

STEP 1: Current loop tuning
  a. Set speed PID output to 0
  b. Inject step current commands (e.g., 0 → 1A → 0A → -1A)
  c. Observe actual current on oscilloscope
  d. Adjust Kp_i and Ki_i for:
     - Rise time < 0.5 ms (for 2 kHz bandwidth)
     - No overshoot (or < 5%)
     - No ringing
     - No audible motor whine

STEP 2: Speed loop tuning
  a. Set position PID output to 0
  b. Inject step speed commands (e.g., 0 → 50 RPM → 0 → -50 RPM)
  c. Observe actual speed (encoder feedback)
  d. Adjust Kp_w and Ki_w for:
     - Rise time < 20 ms (for 50 Hz bandwidth)
     - Overshoot < 10%
     - Steady-state error = 0 (guaranteed by I term)
     - No oscillation under load changes

STEP 3: Position loop tuning
  a. Inject step position commands (e.g., rotate 1 revolution)
  b. Observe actual position
  c. Adjust Kp_pos for:
     - Smooth approach, no overshoot
     - Position held within ±1 encoder count
     - Speed limit not exceeded during slew

PART 6 — INTER-LOOP COORDINATION

6.1 Rate Differences

The loops run at different rates. How do they communicate?

20 kHz (current)     : ─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─┬─
10 kHz (speed)       : ─┬───┬───┬───┬───┬───┬───┬───┬───┬───┬───
1 kHz (position)     : ─┬───────────┬───────────┬───────────┬─────

Implementation: The speed PID runs in the 10 kHz ISR. The current PID runs in the 20 kHz ISR. The position PID runs in a separate 1 kHz timer ISR (or in the main loop at 1 kHz).

Data flow: Each loop reads the most recent setpoint from the loop above it. No synchronization needed because the inner loop always runs faster.

// Shared between ISRs (volatile for compiler)
volatile q16_t speed_setpoint;     // Written by position PID, read by speed PID
volatile q16_t current_setpoint;   // Written by speed PID, read by current PID

// 1 kHz position timer ISR
void position_timer_handler(void) {
    q16_t pos = read_position();
    speed_setpoint = position_pid_compute(&pos_pid, pos_cmd, pos);
}

// 10 kHz speed timer ISR
void speed_timer_handler(void) {
    q16_t spd = compute_speed();
    current_setpoint = speed_pid_compute(&spd_pid, speed_setpoint, spd);
}

// 20 kHz current timer ISR
void current_timer_handler(void) {
    q16_t cur = read_current();
    q16_t duty = current_pi_compute(&cur_pid, current_setpoint, cur);
    set_pwm_duty(duty);
}

6.2 Anti-Windup Across Loops

When the current is saturated (motor at max torque), the speed PID’s integral winds up because speed can’t track the command. Solution:

Back-calculation anti-windup:

// In speed PID, after computing output
q16_t current_cmd_raw = pid->output;  // Before clamping
q16_t current_cmd_clamped = clamp(current_cmd_raw, -I_MAX, I_MAX);

// Back-calculate: reduce integral by the amount that was clamped
q16_t saturation = current_cmd_clamped - current_cmd_raw;
pid->output += q16_mul(pid->back_calc_gain, saturation);

The same applies to the position loop when speed is saturated.


Checkpoint Questions

  1. Why must the current loop be at least 10× faster than the speed loop?
  2. If you only had one PID (position → duty), how would you limit motor current? (Hint: you can’t, easily.)
  3. The speed PID output is clamped to ±3A. What does this mean physically?
  4. Why is the position controller often P-only? What happens if you add an I term?
  5. You tune the speed loop perfectly, then re-tune the current loop. Does the speed loop still work? Why or why not?
  6. Sketch the step response of the entire cascade to a 1-revolution position command. Label the current, speed, and position trajectories.
  7. The motor hits a wall (stall). Describe what each loop does in the next 100 ms.

Key Takeaways

  • Cascade = nested loops: current (fastest) → speed → position (slowest)
  • Each loop limits its output: current PID limits duty, speed PID limits current, position PID limits speed
  • 10:1 bandwidth separation ensures each loop is “transparent” to the one above
  • Tune from inside out: current first, speed second, position last
  • Position loop often needs only P because the plant (speed → position) is already an integrator
  • Anti-windup propagates outward: when an inner loop saturates, outer loop integrals must be managed