Debug Session 1 — Motor Oscillation: “The Wheel Won’t Stop Shaking”

Skills tested: PID tuning, stability analysis, frequency-domain thinking Difficulty: Intermediate Time estimate: 45–60 minutes


The Scenario

Field report from warehouse (Site-A site):

Robot amr-warehouse-08 exhibits a loud buzzing sound from the right wheel at constant speed. The wheel visibly oscillates at ~30 Hz. The left wheel is fine. The robot was working normally yesterday. No firmware or software changes were deployed.

What you have: - Speed PID runs at 1 kHz on the MCU - PID gains: $K_p = 5.0$, $K_i = 25.0$, $K_d = 0.02$ - Encoder: 2048 CPR × 4 (quadrature) = 8192 counts/rev - Motor: 24V DC, 12:1 gearbox - Right motor was replaced last week (maintenance record)


Step 1 — Observe Before Touching

1.1 Data Collection

You SSH into the robot and log speed data for 5 seconds at constant setpoint = 5.0 rad/s:

Time(ms)   Setpoint   Measured    Error    PWM_duty
0          5.000      4.82       0.180    0.412
1          5.000      5.31      -0.310    0.378
2          5.000      4.65       0.350    0.445
3          5.000      5.42      -0.420    0.361
4          5.000      4.53       0.470    0.462
5          5.000      5.55      -0.550    0.340
...

Observation: The measured speed oscillates around the setpoint with growing amplitude. This is an unstable oscillation, not just noise.

1.2 Frequency Analysis

import numpy as np
from scipy.fft import fft, fftfreq

# Load speed data (1000 samples at 1 kHz)
speed_data = np.loadtxt('right_motor_speed.csv')
dt = 0.001
N = len(speed_data)

# Remove mean (DC component)
speed_ac = speed_data - np.mean(speed_data)

# FFT
freqs = fftfreq(N, dt)[:N//2]
spectrum = np.abs(fft(speed_ac))[:N//2] * 2/N

# Find peak frequency
peak_idx = np.argmax(spectrum[1:]) + 1  # Skip DC
peak_freq = freqs[peak_idx]
print(f"Oscillation frequency: {peak_freq:.1f} Hz")
# Result: 33.2 Hz

Key finding: Oscillation at 33.2 Hz. The PID loop runs at 1 kHz, so 33.2 Hz is well within control bandwidth.


Step 2 — Form Hypotheses

# Hypothesis Evidence needed
H1 $K_p$ too high → marginal stability Reduce $K_p$ → does oscillation stop?
H2 Encoder noise → derivative kick Check raw encoder counts, $K_d$ contribution
H3 Mechanical resonance (new motor) Measure with motor disabled (coast down)
H4 Phase lag from computation Measure actual loop timing

Step 3 — Investigate H1: Gain Too High

3.1 The Stability Theory

For a first-order plant (motor + load):

$$G(s) = \frac{K_m}{Js + B}$$

With proportional gain $K_p$, the closed-loop is:

$$T(s) = \frac{K_p K_m}{Js + B + K_p K_m}$$

This is always stable for first-order systems. So why is it oscillating?

Answer: The real system isn’t first order. The encoder measurement, PWM, and motor electrical dynamics add delays. The plant is more like:

$$G(s) = \frac{K_m}{(Js + B)(\tau_e s + 1)} \cdot e^{-s T_{delay}}$$

where $\tau_e$ is the electrical time constant and $T_{delay}$ is the computational + PWM delay.

3.2 Why the Replacement Motor Changed Things

The maintenance record shows the right motor was replaced. The replacement motor has: - Different winding resistance → different electrical time constant $\tau_e$ - Different rotor inertia → different mechanical time constant $J/B$

The old motor (lower inductance, faster electrical response) was stable with these gains. The new motor (higher inductance, slower electrical response) introduces more phase lag → the same gains are now marginally unstable.

3.3 Gain Margin Analysis

import control

# Old motor parameters
Km_old = 0.05   # motor constant
J = 0.005        # inertia
B = 0.01         # friction
tau_e_old = 0.001  # 1 ms electrical time constant

# New motor parameters (higher inductance)
tau_e_new = 0.003  # 3 ms electrical time constant

# Plant transfer functions
G_old = control.tf([Km_old], [J*tau_e_old, J+B*tau_e_old, B])
G_new = control.tf([Km_old], [J*tau_e_new, J+B*tau_e_new, B])

# PID controller (continuous approximation)
Kp, Ki, Kd = 5.0, 25.0, 0.02
C = control.tf([Kd, Kp, Ki], [1, 0])

# Gain and phase margins
gm_old, pm_old, _, _ = control.margin(C * G_old)
gm_new, pm_new, _, _ = control.margin(C * G_new)

print(f"Old motor: Gain margin = {20*np.log10(gm_old):.1f} dB, Phase margin = {pm_old:.1f}°")
print(f"New motor: Gain margin = {20*np.log10(gm_new):.1f} dB, Phase margin = {pm_new:.1f}°")

# Typical result:
# Old motor: Gain margin = 12.3 dB, Phase margin = 45.2°  ← Stable
# New motor: Gain margin = 3.1 dB, Phase margin = 8.7°    ← Barely stable!

Root cause: The new motor’s higher electrical time constant reduced the phase margin from 45° to ~9°, causing marginal instability. The 33 Hz oscillation is the limit cycle at the gain crossover frequency.


Step 4 — Fix It

4.1 Quick Fix: Reduce Kp

Reduce $K_p$ from 5.0 to 3.0. The oscillation stops immediately. But tracking performance degrades.

4.2 Proper Fix: Re-tune for the New Motor

Identify the new motor’s electrical time constant:

# Step response test: apply constant duty, measure current rise
# Current: I(t) = I_ss * (1 - exp(-t/tau_e))
# Fit exponential to find tau_e

from scipy.optimize import curve_fit

def current_model(t, I_ss, tau_e):
    return I_ss * (1 - np.exp(-t / tau_e))

popt, _ = curve_fit(current_model, time_data, current_data, p0=[5.0, 0.002])
tau_e_measured = popt[1]
print(f"Measured tau_e = {tau_e_measured*1000:.2f} ms")
# Result: tau_e = 2.8 ms (confirms the hypothesis)

Re-tune PID for the new motor: - Reduce $K_p$ to 3.5 (restore 35°+ phase margin) - Reduce $K_d$ to 0.008 (less amplification of high-freq noise) - Keep $K_i$ at 25.0 (steady-state accuracy preserved)

4.3 Root Cause Prevention

The real fix: Don’t use fixed PID gains for different motors. Either: 1. Add motor identification to the commissioning procedure 2. Use gain scheduling based on measured motor parameters 3. Store motor-specific PID gains in EEPROM per motor slot


Step 5 — Verify

After re-tuning:

Oscillation amplitude: 0.82 rad/s → 0.05 rad/s (noise floor)
Phase margin: 8.7° → 38.2°
Step response overshoot: 45% → 12%
Settling time: ∞ (oscillating) → 120 ms

Lessons Learned

  1. Motor replacement changes the plant — never assume PID gains transfer between motors.
  2. Oscillation frequency tells you where the instability is. 33 Hz → likely related to electrical time constant or sensor delay, not mechanical resonance (which would be < 10 Hz).
  3. Phase margin < 15° is asking for trouble. Target 30–45° for industrial motors.
  4. Limit cycles (constant-amplitude oscillation) indicate the system is right at the stability boundary. The nonlinearity (PWM saturation) prevents the oscillation from growing to infinity.
  5. Always measure before tuning. The FFT told us the oscillation frequency in 1 second. Without it, we’d be guessing.