Debug Session 2 — Integral Windup: “The Robot Lurches After E-Stop Release”

Skills tested: Anti-windup, integrator dynamics, e-stop recovery Difficulty: Intermediate–Advanced Time estimate: 30–45 minutes


The Scenario

Operator report from warehouse:

After releasing the e-stop button, the robot suddenly lurches forward 20–30 cm before stopping. This happens every time. The e-stop is pressed when the robot is driving forward at 0.3 m/s to stop it near a rack. After clearing the e-stop, the robot jumps forward dangerously close to the rack.

What you have: - Speed PID with anti-windup (supposedly implemented) - E-stop cuts power to motor H-bridges via hardware relay - PID loop continues running during e-stop (software doesn’t know about hardware e-stop immediately) - Anti-windup strategy: integral clamping (output limits ±1.0 duty)


Step 1 — Reproduce and Observe

1.1 Timeline of Events

Time    Event                          Speed_sp  Speed_meas  Integral  PWM_duty
─────────────────────────────────────────────────────────────────────────────
t=0.0   Driving normally               5.0       4.95        0.02      0.38
t=0.5   E-stop pressed (hardware)      5.0       5.0→0       0.02      0.38→0*
        * H-bridge disabled by relay, actual duty = 0 regardless of PWM

t=0.5   PID still running:
        error = 5.0 - 0.0 = 5.0
        integral += 5.0 * 0.001 = 0.005 per ms

t=0.6   integral = 0.02 + 5.0*100ms/1000 = 0.52
t=0.7   integral = 0.52 + 5.0*100ms/1000 = 1.02  → clamped to 1.0
t=0.8   integral = 1.0 (clamped at max)
...
t=3.0   Still clamped at 1.0 (2.5 seconds of e-stop)

t=3.0   E-stop released
        H-bridge re-enabled
        PID output = Kp*error + Ki*integral + Kd*de
                   = 5.0*5.0 + 25.0*1.0 + ...
                   = 25.0 + 25.0 = 50.0  → clamped to 1.0
        PWM duty = 100%  ← FULL POWER LURCH!

1.2 The Problem

The anti-windup clamp limits the integral to keep the output within ±1.0. But 1.0 is still 100% duty cycle! When the e-stop is released, the motor receives full power because: 1. The speed is still 0 (stopped) → large error 2. The integral is at maximum (wound up during e-stop) 3. Both proportional and integral terms point the same direction

The robot accelerates at maximum torque until the speed catches up to the setpoint, overshoots, and eventually settles — but not before lurching forward 20–30 cm.


Step 2 — Why the Anti-Windup Failed

2.1 The Clamp Is Not Anti-Windup

Look at the “anti-windup” code:

// BAD: This is NOT proper anti-windup
float pid_compute(PIDController *pid, float error, float dt) {
    pid->integral += error * dt;

    // Clamp integral
    if (pid->integral > INTEGRAL_MAX) pid->integral = INTEGRAL_MAX;
    if (pid->integral < -INTEGRAL_MAX) pid->integral = -INTEGRAL_MAX;

    float output = pid->Kp * error + pid->Ki * pid->integral + pid->Kd * derivative;

    // Clamp output
    if (output > OUTPUT_MAX) output = OUTPUT_MAX;
    if (output < -OUTPUT_MAX) output = -OUTPUT_MAX;

    return output;
}

The problem: The integral is clamped based on its own range, but it doesn’t know whether the output is actually being applied. During e-stop, the H-bridge is disabled — the output is effectively zero regardless of what PID computes. But the integral keeps accumulating (up to its clamp limit).

True anti-windup requires knowing when the actuator is saturated (or disconnected).

2.2 The Correct Mental Model

During normal operation:        During e-stop:
  Error → PID → Motor            Error → PID → [disconnected]
  Motor → Speed                   Motor → 0
  Speed → Error (closed loop)     0 → Error = LARGE (open loop!)

  Integral grows slowly           Integral grows rapidly
  because error is small          because error is huge and
                                  there's no feedback to reduce it

Step 3 — Fix It

3.1 Fix 1: Back-Calculation Anti-Windup

The integral should track the actual applied output, not the desired output:

float pid_compute_with_back_calc(PIDController *pid, float error, float dt,
                                  bool actuator_enabled) {
    float p_term = pid->Kp * error;
    float d_term = pid->Kd * (error - pid->prev_error) / dt;
    float i_term = pid->Ki * pid->integral;

    float desired_output = p_term + i_term + d_term;

    // Clamp to actuator limits
    float actual_output = clamp(desired_output, -OUTPUT_MAX, OUTPUT_MAX);

    // If actuator is disabled (e-stop), effective output is 0
    if (!actuator_enabled) {
        actual_output = 0.0f;
    }

    // Back-calculation: adjust integral based on what was actually applied
    float saturation_error = actual_output - desired_output;
    pid->integral += error * dt + (saturation_error / pid->Ki) * pid->Kb;

    pid->prev_error = error;
    return actual_output;
}

$K_b$ (back-calculation gain) determines how fast the integral “unwinds.” Typical: $K_b = 1/T_i$ where $T_i = K_p/K_i$.

3.2 Fix 2: Reset Integral on E-Stop

Simpler and more robust for the robot case:

// In the main control loop
void control_loop(void) {
    if (estop_active()) {
        // Reset integral to zero during e-stop
        pid_reset_integral(&speed_pid_left);
        pid_reset_integral(&speed_pid_right);

        // Also reset setpoint to zero
        speed_setpoint_left = 0.0f;
        speed_setpoint_right = 0.0f;
        return;  // Don't compute PID output
    }

    // Normal PID operation
    // ...
}

3.3 Fix 3: Ramp Setpoint After E-Stop Release

Even with integral reset, the proportional term will cause a jump if the setpoint is still non-zero:

void post_estop_recovery(void) {
    static float ramp_factor = 0.0f;

    if (estop_just_released()) {
        ramp_factor = 0.0f;  // Start from zero
    }

    if (ramp_factor < 1.0f) {
        ramp_factor += RAMP_RATE * dt;  // e.g., RAMP_RATE = 2.0 → 500ms to full speed
        if (ramp_factor > 1.0f) ramp_factor = 1.0f;
    }

    // Apply ramp to setpoint
    float effective_setpoint = cmd_setpoint * ramp_factor;

    float output = pid_compute(&speed_pid, effective_setpoint, speed_measured);
}

AMR implements all three: Reset integral on e-stop, ramp setpoint on release, and back-calculation anti-windup during normal operation.


Step 4 — Verify

4.1 Before Fix

t=3.0 (e-stop release):
  Speed: 0 → 7.2 rad/s in 50ms (overshoot 44%)
  Position: +22 cm lurch
  Current: peaks at 15A (overcurrent warning)

4.2 After Fix (all three measures)

t=3.0 (e-stop release):
  Speed: 0 → ramps to 5.0 over 500ms (no overshoot)
  Position: smooth acceleration, no lurch
  Current: peaks at 3A (normal)

Step 5 — The Deeper Lesson

5.1 Where Else Does This Happen?

Integral windup occurs whenever the control loop is broken:

Situation Loop broken because Effect
E-stop Actuator disconnected Lurch on release
Motor stall Torque limit reached, speed=0 Lurch when unstalled
Wheel in the air No load → speed maxes instantly Slam when wheel touches ground
Mode switch Controller changes from position to speed mode Spike at mode transition
Sensor failure Measured value freezes or jumps Integral diverges

5.2 The Golden Rule

If the actuator can’t do what the controller wants, the integral must know about it.

This is the fundamental principle of anti-windup. The integral should only accumulate error when the system is actually responding to the control effort.


Checkpoint Questions

  1. Why doesn’t clamping the integral term prevent windup during e-stop?
  2. The integral accumulated to 1.0 during 2.5 seconds of e-stop with error = 5.0 and Ki = 25.0. Show the math: $1.0 = 25.0 \times 5.0 \times t_{windup}$. Solve for $t_{windup}$.
  3. Back-calculation anti-windup uses a gain $K_b$. If $K_b$ is too large, what happens? Too small?
  4. Why does AMR reset the setpoint to zero during e-stop (not just the integral)?
  5. A robot wheel lifts off the ground during a ramp ascent. The speed PID winds up. What happens when the wheel touches down again?